Mathematical Problems in Engineering
Volume 2012 (2012), Article ID 873840, 14 pages
http://dx.doi.org/10.1155/2012/873840
Research Article

Evaluation of Aerosol Fire Extinguishing Agent Using a Simple Diffusion Model

School of Chemical Engineering, Nanjing University of Science and Technology, Nanjing 210094, China

Received 21 July 2012; Accepted 24 September 2012

Academic Editor: Bin Liu

Copyright © 2012 Chen-guang Zhu et al. This is an open access article distributed under the Creative Commons Attribution License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.

Abstract

Aerosol fire extinguishing agents have been recognized as an effective replacement of Halon. The uniform diffusion time and the effective concentration of the aerosol fire extinguishing agent are important parameters for putting out a fire. In this work, the effective concentration is derived based on the diffusion equation, and its variation with changing diffusion coefficient and diffusion time is analyzed. The uniform diffusion time could then be conveniently estimated using this equation. Based on experimental data, the concentration kinetics of the aerosol is drawn and the relation between the diffusion coefficient and the uniform diffusion time is analyzed. It was found that the uniform diffusion time is not dependent on the shape of the closed room but dependent on the total room volume and the position of its diffusion source. This model is demonstrated as a facile tool for the convenient evaluation and reasonable application of the aerosol fire extinguishing agent by predicting the uniform diffusion times of extinguishing aerosol in closed rooms.